Fehlerstrom-Schutzschalter Siemens AG

Zur Auswahl hinzufügen
Allgemeine Information
YESSS-Bestellnummer
3071-2617
Produktcode
5SV33446GV02
EAN-Code
04001869510910
Produktgruppe
Fehlerstrom-Schutzschalter
Marke
Siemens AG
Typ
RCCB
RCCB, 4-pole, type A, In: 40 A, 30 mA, Un RCCB, 4-pole, type A, In: 40 A, 30 mA, Un AC: 400 V, bulk packaging
Produktbeschreibung

Residual current operated circuit breaker, 4-pole, type A, In: 40 A, 30 mA, Un AC: 400 V, Bulk packaging 18 units RCCB SENTRON 5SV3 for comprehensive protection against electric shock for personnel and property. The RCCBs provide reliable safety in the installation due to the reach-around and touch protection that they contain as standard. Simply by operating a manual slide, you can remove the RCCB from the DIN rail or the busbar assembly without the use of a tool. Via the Data Matrix code on the device, you can gain fast access to all technical data in the Siemens Industry Online Support App. The SENTRON protective switching devices can be expanded by many additional functions with consistent accessories from the modular system. Optimized technology for your safety - only from Siemens.

Produktspezifikationen
Polzahl
4
Bemessungsspannung
400 V
Bemessungsstrom
40 A
Bemessungsisolationsspannung Ui
2000 V
Bemessungsstoßspannungsfestigkeit Uimp
6 kV
Fehlerstrom-Typ
A
Selektiver-Typ
Nein
Kurzzeitverzögerter Typ
Nein
Kurzschlussfestigkeit (Icw)
10 kA
Stoßstromfestigkeit
1 kA
Frequenz
50 Hz
Zusatzeinrichtungen möglich
Ja
Mit Verriegelungsvorrichtung
Ja
Breite in Teilungseinheiten
4
Einbautiefe
70 mm
Umgebungstemperatur während des Betriebs
-25 - 45 °C
Verschmutzungsgrad
2
Anschließbarer Leiterquerschnitt mehrdrähtig
0.75 - 35 mm²
Anschließbarer Leiterquerschnitt eindrähtig
0.75 - 35 mm²
Bemessungsfehlerstrom
0.03 A
Spannungsart
AC
Explosionsgeschützt
Nein
weitere spezifikationen
^